DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-1917613669560

Start Test Date:07-NOV-2013 0758Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):2071
Discharge Rate (gal/min):125Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1520Storativity:
Tested Interval Max. (ft BLS):1610Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):7.9
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:



SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-1917613669560

Start Test Date:11-NOV-2013 1114Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):1109
Discharge Rate (gal/min):118.5Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1310Storativity:
Tested Interval Max. (ft BLS):1400Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):4.1
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:



SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-1917613669560

Start Test Date:15-NOV-2013 0830Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):3444
Discharge Rate (gal/min):113.7Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1165Storativity:
Tested Interval Max. (ft BLS):1250Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):13.1
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:



SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-1917613669560

Start Test Date:25-NOV-2013 1257Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):2656
Discharge Rate (gal/min):125Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1018Storativity:
Tested Interval Max. (ft BLS):1230Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):9.8
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:

Page generated at: 04-OCT-2025 06:39 EDT