DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-2916894669089

Start Test Date:30-JUN-2014 0000Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:APTTransmissivity (ft2/day):20736
Discharge Rate (gal/min):1050Horizontal K (ft/day):
Hours Pumped:8Vertical K (ft/day):
Tested Interval Min. (ft BLS):1035Storativity:.00003
Tested Interval Max. (ft BLS):1250Leakance (1/day):
No. Monitored Wells:1Specific Capacity (gpm/ft):12.4
SourceReferenceCitation Id
CONSULTANT MWH, MARCH 2015, FLORIDAN TEST WELLS FW-1 AND FW-2, CONSTRUCTION AND TESTING REPORT, BCWTP1A EXPANSION311
Comments:



SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-2916894669089

Start Test Date:16-MAR-2014 1110Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):720.1
Discharge Rate (gal/min):98.3Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1350Storativity:
Tested Interval Max. (ft BLS):1300Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):2.5
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:



SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-2916894669089

Start Test Date:07-MAY-2014 1155Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):554.4
Discharge Rate (gal/min):97.2Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1400Storativity:
Tested Interval Max. (ft BLS):1450Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):2
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:



SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-2916894669089

Start Test Date:07-MAY-2014 1710Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):2527
Discharge Rate (gal/min):105Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1500Storativity:
Tested Interval Max. (ft BLS):1600Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):9.1
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:



SitePumped WellX-Coord(ft)Y-Coord (ft)
BROWARD COUNTY WATER TREATMENT PLANT 1ABCWTP1FW-2916894669089

Start Test Date:12-MAY-2014 0846Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):4798
Discharge Rate (gal/min):477Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1000Storativity:
Tested Interval Max. (ft BLS):1200Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):17.2
SourceReferenceCitation Id
CONSULTANT MWH. March 2015. Floridan Test Wells FW-1 and FW-2 Construction and Testing Report; Broward County WTP 1A Expansion311
Comments:

Page generated at: 04-OCT-2025 11:43 EDT

DBHYDRO Menu  |   DBHYDRO Home  |   SFWMD Home  |   User's Guide  |   What's New  |   FAQ |  Comments?