Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
BELLE GLADE FAS WELLFIELD AT PAUL RARDIN PARKBGTP-1759842877797

Start Test Date:20-MAR-2005 0000Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:APTTransmissivity (ft2/day):15854
Discharge Rate (gal/min):1432Horizontal K (ft/day):
Hours Pumped:72Vertical K (ft/day):
Tested Interval Min. (ft BLS):1150Storativity:.00011
Tested Interval Max. (ft BLS):1450Leakance (1/day):.002
No. Monitored Wells:1Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT CDM, MAY, 2005. PALM BEACH COUNTY WATER UTILITIES DEPARTMENT PAUL RARDIN PARK TEST PRODUCTION WELLS TP-1 & TP-2 COMPLETION REPORT.
Comments:TEST WAS CONDUCTED POST ACIDIFICATION OF THE WELLS. THE MONITOR WELL, TP-2, WAS ALSO PUMPED AT A CONSTANT RATE OF 50 GPM DURING THE TEST. RESULTS ARE BASED ON HANTUSH & JACOB (1955) METHOD FOR A LEAKY CONFINED AQUIFER. SALINITY FROM THE TESTED INTERVAL ~ 2,500 MG/L TDS.