DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
MELBOURNE LAKE WASHINGTON
BR-0907
742211
1387442
Start Test Date:
16-OCT-1989 1717
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
APT
Transmissivity (ft2/day):
34577
Discharge Rate (gal/min):
2070
Horizontal K (ft/day):
Hours Pumped:
92
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
240
Storativity:
.0012
Tested Interval Max. (ft BLS):
550
Leakance (1/day):
No. Monitored Wells:
2
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
HYDRO DESIGNS. 1990. FLORIDAN AQUIFER WELLFIELD STUDY DATA COLLECTION AND EVALUATION REPORT. PREPARED FOR SMITH & GILLESPIE ENGINEERS, INC.
Comments:
PARAMETER VALUES ARE MEANS FROM MONITORING WELLS. SEE ANALYSIS INFO FOR INDIVIDUAL DATA. IN ANALYSIS INFO, IN STATION BR-0916 RECOVERY METHOD, THE TRANS VALUE IS MEAN OF 197000 TO 394000.
Well Name
X Coord(ft)
Y Coord(ft)
Analysis Method
DistancefromProductionWell(ft)
Max.Drawdown(ft)
Transmissivity(ft**2/day)
Storativity
Leakance
BR-0910
742261
1387442
RECOVERY
50
72995
.0005
BR-0910
742261
1387442
UNKNOWN
50
26070
.0016
BR-0916
742476
1387442
RECOVERY
265
39505
.0008
BR-0916
742476
1387442
UNKNOWN
265
75267
.00058
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
MELBOURNE LAKE WASHINGTON
BR-0907
742211
1387442
Start Test Date:
28-DEC-1989 0000
Aquifer:
AVON-PARK PERMEABLE ZONE
Test Type:
APT
Transmissivity (ft2/day):
339553
Discharge Rate (gal/min):
2320
Horizontal K (ft/day):
Hours Pumped:
744
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
240
Storativity:
.00064
Tested Interval Max. (ft BLS):
864
Leakance (1/day):
.0000066
No. Monitored Wells:
3
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
HYDRO DESIGNS. 1990. FLORIDAN AQUIFER WELLFIELD STUDY DATA COLLECTION AND EVALUATION REPORT. PREPARED FOR SMITH & GILLESPIE ENGINEERS, INC.
Comments:
TRANS AND STORATIVITY VALUES ARE MEANS FROM MONITOR WELLS. NO UNITS FOR LEAKANCE WERE GIVEN IN REPORT. TRANSMISSIVITY REPORTED IN GPD/FT AND ASSUMING CONVERSION OF UNITS IS CONSISTANT, LEAKANCE WAS REPORTED AS GPD/CUBIC FEET. LEAKANCE GIVEN HERE IN UNITS OF PER DAY (DAY-1).
Well Name
X Coord(ft)
Y Coord(ft)
Analysis Method
DistancefromProductionWell(ft)
Max.Drawdown(ft)
Transmissivity(ft**2/day)
Storativity
Leakance
BR-0910
742261
1387442
RECOVERY
50
601604
.0001
.0000066
BR-0916
742476
1387442
RECOVERY
265
941176
.00015
BR-0916
742476
1387442
UNKNOWN
265
846257
.00024
BR-0915
744711
1387442
RECOVERY
2500
1336898
.0023
Page generated at: 04-OCT-2025 11:44 EDT