DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
BURMA RD: SEACOAST UTILITY AUTHORITYBURMA-TEST953102897638

Start Test Date:03-FEB-1988 1100Aquifer:SURFICIAL AQUIFER SYSTEM
Test Type:APTTransmissivity (ft2/day):6518
Discharge Rate (gal/min):213Horizontal K (ft/day):
Hours Pumped:24Vertical K (ft/day):
Tested Interval Min. (ft BLS):132Storativity:
Tested Interval Max. (ft BLS):162Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT GERAGHTY AND MILLER, 1988, GERAGHTY & MILLER, MARCH 1998, DRILLING AND TESTING OF TEST WELLS AT BURMA ROAD AND LAKE CATHERINE, PALM BEACH COUNTY, FLORIDA, PREPARED FOR SUNCOAST UTILITIES
Comments:CALCULATED USING JACOB METHOD

Well Name X Coord
(ft)
Y Coord
(ft)
Analysis Method Distance
from
Production
Well
(ft)
Max.
Drawdown
(ft)
Transmissivity
(ft**2/day)
Storativity Leakance
BURMA-2D
953013
897435
OTHER
200
9426
.00026
.35
BURMA-3D
952925
897131
OTHER
500
34141
.00091
.44
BURMA-4D
953374
897639
OTHER
250
8934
.00073
1.06

Page generated at: 04-OCT-2025 10:09 EDT

DBHYDRO Menu  |   DBHYDRO Home  |   SFWMD Home  |   User's Guide  |   What's New  |   FAQ |  Comments?