SitePumped WellX-Coord(ft)Y-Coord (ft)
CAPE CORAL REVERSE OSMOSIS WELLFIELDCCRO-9326927815302

Start Test Date:28-MAR-1983 0000Aquifer:LOWER HAWTHORN PRODUCING ZONE
Test Type:APTTransmissivity (ft2/day):4743
Discharge Rate (gal/min):746Horizontal K (ft/day):
Hours Pumped:240Vertical K (ft/day):
Tested Interval Min. (ft BLS):350Storativity:.003
Tested Interval Max. (ft BLS):748Leakance (1/day):
No. Monitored Wells:2Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT LAYNE-WESTERN COMPANY. 1983. AQUIFER TEST REPORT. LOWER HAWTHORNE AQUIFER, CAPE CORAL, FL.
Comments:IN ANALYSIS INFO FOR STATIONS AT CCRO-9, CCRO-9A, AND CCRO-9B, THE METHOD USED LISTED AS OTHER IS TIME-DRAWDOWN ALSO BUT PLOTTED ON LOG-LOG SCALE INSTEAD OF THE SEMI-LOG PLOT THAT THE PREVIOUS RESULTS ARE IN.

Well Name X Coord
(ft)
Y Coord
(ft)
Analysis Method Distance
from
Production
Well
(ft)
Max.
Drawdown
(ft)
Transmissivity
(ft**2/day)
Storativity Leakance
CCRO-9
326927
815302
OTHER
4626
.0054
.0047
CCRO-9
326927
815302
TIME DRAWDOWN
4706
CCRO-9A
326864
815412
OTHER
71
5080
.0016
.0067
CCRO-9A
326864
815412
TIME DRAWDOWN
71
5063
.00023
CCRO-9B
326864
816041
OTHER
700
12433
.002
.0023
CCRO-9B
326864
816041
TIME DRAWDOWN
700
14231
.0002

Page generated at: 04-OCT-2025 06:35 EDT