DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FAS
CCUEP-IW-2
318259
961261
Start Test Date:
22-APR-1996 0930
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
OTHER
Transmissivity (ft2/day):
135501
Discharge Rate (gal/min):
5252
Horizontal K (ft/day):
Hours Pumped:
24
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2965
Storativity:
Tested Interval Max. (ft BLS):
3246
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
VIROGROUP, INC, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-1, JANUARY 1997
Comments:
INJECTION TEST, DISCHARGE RATE IS INJECTION RATE, TRANSMISSIVITY VALUE IS AN AVERAGE BASED ON ANALYSIS OF SEMILOG PLOT OF PRESSURE VERSUS THE LOG OF REDUCED TIME.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FAS
CCUEP-IW-2
318259
961261
Start Test Date:
27-NOV-1995 0000
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
94
Horizontal K (ft/day):
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1526
Storativity:
Tested Interval Max. (ft BLS):
1575
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2 VOLUME 1
Comments:
PACKER TEST 1 OF 5 TEST RUN FOR WATER QUALITY TO DETERMINE USDW ONLY
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FAS
CCUEP-IW-2
318259
961261
Start Test Date:
29-NOV-1995 0000
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
83
Horizontal K (ft/day):
Hours Pumped:
3
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1610
Storativity:
Tested Interval Max. (ft BLS):
1654
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2
Comments:
PACKER TEST 2 OF 5 TEST RUN FOR WATER QUALITY TO DETERMINE USDW ONLY
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FAS
CCUEP-IW-2
318259
961261
Start Test Date:
28-FEB-1996 0000
Aquifer:
MIDDLE FAS CONFINING UNIT
Test Type:
PACKER
Transmissivity (ft2/day):
1992
Discharge Rate (gal/min):
65
Horizontal K (ft/day):
47.43
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2013
Storativity:
Tested Interval Max. (ft BLS):
2055
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2 VOLUME 1
Comments:
PACKER TEST 3 OF 5 TRANSMISSIVITY CALCULATED USING COOPER-JACOB (1946)
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FAS
CCUEP-IW-2
318259
961261
Start Test Date:
01-MAR-1996 0000
Aquifer:
MIDDLE FAS CONFINING UNIT
Test Type:
PACKER
Transmissivity (ft2/day):
576
Discharge Rate (gal/min):
90
Horizontal K (ft/day):
15.57
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2280
Storativity:
Tested Interval Max. (ft BLS):
2317
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2
Comments:
PACKER TEST 4 OF 5
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FAS
CCUEP-IW-2
318259
961261
Start Test Date:
05-MAR-1996 0000
Aquifer:
MIDDLE FAS CONFINING UNIT
Test Type:
PACKER
Transmissivity (ft2/day):
3699
Discharge Rate (gal/min):
95
Horizontal K (ft/day):
51.38
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2743
Storativity:
Tested Interval Max. (ft BLS):
2815
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2 VOLUME 1
Comments:
PACKER TEST 5 OF 5 TRANSMISSIVITY WAS CALCULATED USING COOPER-JACOB (1946)
Page generated at: 01-JUL-2024 06:40 EDT