DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FASCCUEP-IW-2318259961261

Start Test Date:22-APR-1996 0930Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:OTHERTransmissivity (ft2/day):135501
Discharge Rate (gal/min):5252Horizontal K (ft/day):
Hours Pumped:24Vertical K (ft/day):
Tested Interval Min. (ft BLS):2965Storativity:
Tested Interval Max. (ft BLS):3246Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT VIROGROUP, INC, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-1, JANUARY 1997
Comments:INJECTION TEST, DISCHARGE RATE IS INJECTION RATE, TRANSMISSIVITY VALUE IS AN AVERAGE BASED ON ANALYSIS OF SEMILOG PLOT OF PRESSURE VERSUS THE LOG OF REDUCED TIME.



SitePumped WellX-Coord(ft)Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FASCCUEP-IW-2318259961261

Start Test Date:27-NOV-1995 0000Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):
Discharge Rate (gal/min):94Horizontal K (ft/day):
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):1526Storativity:
Tested Interval Max. (ft BLS):1575Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2 VOLUME 1
Comments:PACKER TEST 1 OF 5 TEST RUN FOR WATER QUALITY TO DETERMINE USDW ONLY



SitePumped WellX-Coord(ft)Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FASCCUEP-IW-2318259961261

Start Test Date:29-NOV-1995 0000Aquifer:UPPER FLORIDAN AQUIFER (UFA)
Test Type:PACKERTransmissivity (ft2/day):
Discharge Rate (gal/min):83Horizontal K (ft/day):
Hours Pumped:3Vertical K (ft/day):
Tested Interval Min. (ft BLS):1610Storativity:
Tested Interval Max. (ft BLS):1654Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2
Comments:PACKER TEST 2 OF 5 TEST RUN FOR WATER QUALITY TO DETERMINE USDW ONLY



SitePumped WellX-Coord(ft)Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FASCCUEP-IW-2318259961261

Start Test Date:28-FEB-1996 0000Aquifer:MIDDLE FAS CONFINING UNIT
Test Type:PACKERTransmissivity (ft2/day):1992
Discharge Rate (gal/min):65Horizontal K (ft/day):47.43
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):2013Storativity:
Tested Interval Max. (ft BLS):2055Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2 VOLUME 1
Comments:PACKER TEST 3 OF 5 TRANSMISSIVITY CALCULATED USING COOPER-JACOB (1946)



SitePumped WellX-Coord(ft)Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FASCCUEP-IW-2318259961261

Start Test Date:01-MAR-1996 0000Aquifer:MIDDLE FAS CONFINING UNIT
Test Type:PACKERTransmissivity (ft2/day):576
Discharge Rate (gal/min):90Horizontal K (ft/day):15.57
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):2280Storativity:
Tested Interval Max. (ft BLS):2317Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2
Comments:PACKER TEST 4 OF 5



SitePumped WellX-Coord(ft)Y-Coord (ft)
CHARLOTTE CTY UTILITIES EAST PORT INJECTION -FASCCUEP-IW-2318259961261

Start Test Date:05-MAR-1996 0000Aquifer:MIDDLE FAS CONFINING UNIT
Test Type:PACKERTransmissivity (ft2/day):3699
Discharge Rate (gal/min):95Horizontal K (ft/day):51.38
Hours Pumped:4Vertical K (ft/day):
Tested Interval Min. (ft BLS):2743Storativity:
Tested Interval Max. (ft BLS):2815Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT VIROGROUP INC., JANUARY 1997, EAST PORT WATER RECLAMATION FACILITY COMPLETION REPORT FOR IW-2 VOLUME 1
Comments:PACKER TEST 5 OF 5 TRANSMISSIVITY WAS CALCULATED USING COOPER-JACOB (1946)

Page generated at: 01-JUL-2024 06:40 EDT

DBHYDRO Menu  |   DBHYDRO Home  |   SFWMD Home  |   User's Guide  |   What's New  |   FAQ |  Comments?