DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
CLEWISTON RO WELLFIELD
CLEWRO-PW2
675831
875040
Start Test Date:
13-DEC-2005 0000
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
APT
Transmissivity (ft2/day):
12800
Discharge Rate (gal/min):
964
Horizontal K (ft/day):
Hours Pumped:
48
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
700
Storativity:
.00043
Tested Interval Max. (ft BLS):
1200
Leakance (1/day):
.0008
No. Monitored Wells:
2
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CDM, 2006. CITY OF CLEWISTON WATER TREATMENT PLANT PRODUCTION WELLS PW-1 AND PW-2, COMPLETION REPORT. APRIL 2006.
Comments:
PUMP FAILED AFTER 2 DAYS OF PUMPING, NO COLLECTION OF RECOVERY DATA. CHLORIDE CONCENTRATION AT END OF TEST = 1140 MG/L.