DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
CW Combee Water Treatment PlantCOMBEE3626721372343

Start Test Date:01-APR-2006 0000Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:APTTransmissivity (ft2/day):77300
Discharge Rate (gal/min):2900Horizontal K (ft/day):
Hours Pumped:263Vertical K (ft/day):
Tested Interval Min. (ft BLS):300Storativity:.00022
Tested Interval Max. (ft BLS):581Leakance (1/day):.00016
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
 
Comments:Drawdown and recovery monitored at six wells including the production well; data corrected for regional trends; analysis performed using Theis (1935) drawdwon / recovery, Hantush-Jacob (1955)