DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
06-FEB-1012 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
APT
Transmissivity (ft2/day):
33144
Discharge Rate (gal/min):
1894
Horizontal K (ft/day):
Hours Pumped:
48
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
962
Storativity:
.0005
Tested Interval Max. (ft BLS):
1570
Leakance (1/day):
No. Monitored Wells:
1
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
AECOM, MAY 2012
Comments:
INTERVAL OPEN TO UF AND APPZ
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
06-DEC-2011 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
67.2
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1575
Storativity:
Tested Interval Max. (ft BLS):
1590
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
.98
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:8076 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
08-DEC-2011 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
53.4
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1582
Storativity:
Tested Interval Max. (ft BLS):
1590
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
.77
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:7569 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
13-DEC-2011 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
75.6
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1430
Storativity:
Tested Interval Max. (ft BLS):
1465
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
2.2
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:8700 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
14-DEC-2011 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
75.5
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1332
Storativity:
Tested Interval Max. (ft BLS):
1367
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
4.3
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:10420 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
15-DEC-2011 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
72.4
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1235
Storativity:
Tested Interval Max. (ft BLS):
1270
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
.67
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:87664 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
09-JAN-2012 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
1789
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
962
Storativity:
Tested Interval Max. (ft BLS):
1590
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
65.3
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:8177 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
10-JAN-2012 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
1263
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
962
Storativity:
Tested Interval Max. (ft BLS):
1500
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
31.7
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:8981 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
10-JAN-2012 0100
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
1047
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
962
Storativity:
Tested Interval Max. (ft BLS):
1400
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
27.3
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:6375 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
11-JAN-2012 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
746
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
962
Storativity:
Tested Interval Max. (ft BLS):
1300
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
19.6
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:8142 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
11-JAN-2012 0100
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
647
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
962
Storativity:
Tested Interval Max. (ft BLS):
1200
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
17.1
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:8153 uS/cm
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF DAVIE FLORIDAN TEST PRODUCTION
DAVIE-PW3
904925
636925
Start Test Date:
12-JAN-2012 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
548
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
962
Storativity:
Tested Interval Max. (ft BLS):
1130
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
14.2
Source
Reference
Citation Id
CONSULTANT
AECOM, May 2013
Comments:
Field Specific Conductance:7545 uS/cm