DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - STOCK ISLAND
FKAA-SIASR
412251
82410
Start Test Date:
17-FEB-1993 0830
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
APT
Transmissivity (ft2/day):
256.4
Discharge Rate (gal/min):
198.6
Horizontal K (ft/day):
Hours Pumped:
24
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
680
Storativity:
Tested Interval Max. (ft BLS):
716
Leakance (1/day):
No. Monitored Wells:
1
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, FEBRUARY 1993, LETTER REPORT ASR TEST PROGRAM AT STOCK ISLAND, FLORIDA
Comments:
T VALUE IS AVERAGE OF METHODS USED, SEE ANALYSIS
Well Name
X Coord(ft)
Y Coord(ft)
Analysis Method
DistancefromProductionWell(ft)
Max.Drawdown(ft)
Transmissivity(ft**2/day)
Storativity
Leakance
FKAA-SIASR
412251
82410
COOPER-JACOB APPROXIMATION
0
55
282.4
FKAA-SIASR
412251
82410
THEIS RECOVERY
0
55
155.6
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - STOCK ISLAND
FKAA-SIASR
412251
82410
Start Test Date:
01-NOV-1991 0000
Aquifer:
Test Type:
SPECIFIC CAPACITY
Transmissivity (ft2/day):
867.2
Discharge Rate (gal/min):
170
Horizontal K (ft/day):
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
680
Storativity:
Tested Interval Max. (ft BLS):
715
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, MARCH 1992, FLORIDA KEYS ASR TEST PROGRAM AT STOCK ISLAND
Comments:
ESTIMATES OF TRANSMISSIVITY WERE MADE FROM A METHOD PRESENTED BY DRISCOLL (1986) RELATING SPECIFIC CAPACITY AND AQUIFER CONDITIONS ACCORDING TO THE EQUATION: T = 2000 Q/S
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - STOCK ISLAND
FKAA-SIASR
412251
82410
Start Test Date:
05-NOV-1991 0001
Aquifer:
Test Type:
SPECIFIC CAPACITY
Transmissivity (ft2/day):
2466
Discharge Rate (gal/min):
700
Horizontal K (ft/day):
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
680
Storativity:
Tested Interval Max. (ft BLS):
750
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, MARCH 1992, FLORIDA KEYS ASR TEST PROGRAM AT STOCK ISLAND
Comments:
ESTIMATES OF TRANSMISSIVITY WERE MADE FROM A METHOD PRESENTED BY DRISCOLL (1986) RELATING SPECIFIC CAPACITY AND AQUIFER CONDITIONS ACCORDING TO THE EQUATION: T = 2000 Q/S
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - STOCK ISLAND
FKAA-SIASR
412251
82410
Start Test Date:
05-NOV-1991 0002
Aquifer:
Test Type:
SPECIFIC CAPACITY
Transmissivity (ft2/day):
2710
Discharge Rate (gal/min):
450
Horizontal K (ft/day):
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
680
Storativity:
Tested Interval Max. (ft BLS):
750
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, MARCH 1992, FLORIDA KEYS ASR TEST PROGRAM AT STOCK ISLAND
Comments:
ESTIMATES OF TRANSMISSIVITY WERE MADE FROM A METHOD PRESENTED BY DRISCOLL (1986) RELATING SPECIFIC CAPACITY AND AQUIFER CONDITIONS ACCORDING TO THE EQUATION: T = 2000 Q/S
Page generated at: 04-OCT-2025 11:50 EDT