DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - JR DEAN WATER TREATMENT PLANT
FKAAFC-FA1
818329
402527
Start Test Date:
26-JUL-2007 1030
Aquifer:
Test Type:
APT
Transmissivity (ft2/day):
29819
Discharge Rate (gal/min):
2550
Horizontal K (ft/day):
Hours Pumped:
72
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
Storativity:
Tested Interval Max. (ft BLS):
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, 2007, WELL COMPLETION REPORT
Comments:
APT INFORMAITON IS SKETCHY
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - JR DEAN WATER TREATMENT PLANT
FKAAFC-FA1
818329
402527
Start Test Date:
10-JAN-2007 0800
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
75
Discharge Rate (gal/min):
50
Horizontal K (ft/day):
Hours Pumped:
8
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1045
Storativity:
Tested Interval Max. (ft BLS):
1130
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
.4
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, 2007, WELL COMPLETION REPORT
Comments:
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - JR DEAN WATER TREATMENT PLANT
FKAAFC-FA1
818329
402527
Start Test Date:
07-FEB-2007 0700
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
187
Discharge Rate (gal/min):
571
Horizontal K (ft/day):
Hours Pumped:
10
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
880
Storativity:
Tested Interval Max. (ft BLS):
1000
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
3.3
Source
Reference
Citation Id
CONSULTANT
CH2MHILL,2007 WELL COMPLETION REPORT
Comments:
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FKAA - JR DEAN WATER TREATMENT PLANT
FKAAFC-FA1
818329
402527
Start Test Date:
03-MAR-2007 1000
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
549
Discharge Rate (gal/min):
920
Horizontal K (ft/day):
Hours Pumped:
12
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
880
Storativity:
Tested Interval Max. (ft BLS):
1040
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
7
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, 2007, WELL COMPLETION REPORT
Comments:
Page generated at: 04-OCT-2025 13:59 EDT