DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FT. MYERS REVERSE OSMOSIS WATER TREATMENT PLANT
FTM_RO-P4
387001
832902
Start Test Date:
09-NOV-2000 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
APT
Transmissivity (ft2/day):
8490
Discharge Rate (gal/min):
2400
Horizontal K (ft/day):
27
Hours Pumped:
24
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
480
Storativity:
.00018
Tested Interval Max. (ft BLS):
832
Leakance (1/day):
.0009
No. Monitored Wells:
2
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2M HILL, MARCH 2001, CONSTRUCTION AND TESTING OF PROD. WELLS P-3 THROUGH P-7, FT. MYERS, FL
Comments:
TRANSMISSIVITY, STORATIVITY AND LEAKANCE ARE AVERAGES OF CJ, THEIS AND THEIS RECOVERY METHODS.
Page generated at: 24-NOV-2024 20:37 EDT