DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
FT. MYERS REVERSE OSMOSIS WATER TREATMENT PLANT
FTM_RO-P6
387001
830402
Start Test Date:
19-OCT-2000 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
APT
Transmissivity (ft2/day):
21260
Discharge Rate (gal/min):
2300
Horizontal K (ft/day):
60
Hours Pumped:
24
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
445
Storativity:
.0004
Tested Interval Max. (ft BLS):
805
Leakance (1/day):
.0005
No. Monitored Wells:
2
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2M HILL, MARCH 2001, CONSTRUCTION AND TESTING OF PROD. WELLS P-3 THROUGH P-7, FT. MYERS, FL
Comments:
TRANSMISSIVITY, STORATIVITY AND LEAKANCE VALUES ARE AVERAGES OF CJ, THEIS AND THEIS RECOVERY METHODS.