DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF HIGHLAND BEACH RO WTP
HB-TPW1
961556
755843
Start Test Date:
03-AUG-2001 0000
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
APT
Transmissivity (ft2/day):
13182
Discharge Rate (gal/min):
3000
Horizontal K (ft/day):
.0000094
Hours Pumped:
72
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1027
Storativity:
Tested Interval Max. (ft BLS):
1200
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2M HILL, OCTOBER 2001, TECH. MEMORANDUM- CONSTRUCTION & TESTING OF FLORIDAN AQUIFER TEST PRODUCTION WELL TP-1
Comments:
VALUES ARE AVERAGE OF PUMPED AND RECOVERY DATA ANALYSIS METHOD: COOPER-JACOB TDS: 6600 MG/L
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF HIGHLAND BEACH RO WTP
HB-TPW1
961556
755843
Start Test Date:
09-AUG-2001 0000
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
330
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1030
Storativity:
Tested Interval Max. (ft BLS):
1110
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
TECH. MEMORANDUM- CONSTRUCTION & TESTING OF FLORIDAN AQUIFER TEST PRODUCTION WELL TP-1
Comments:
PACKER TEST 1 CONDUCTED FOR WQ AND SPECIFIC CAPACITY S.C.= 12.5 GPM/FT
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF HIGHLAND BEACH RO WTP
HB-TPW1
961556
755843
Start Test Date:
09-AUG-2001 0100
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
575
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1030
Storativity:
Tested Interval Max. (ft BLS):
1200
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2M HILL, OCTOBER 2001, TECH. MEMORANDUM- CONSTRUCTION & TESTING OF FLORIDAN AQUIFER TEST PRODUCTION WELL TP-1
Comments:
PACKER TEST 2 CONDUCTED FOR WQ AND SPECIFIC CAPACITY S.C.= 23.7 GPM/FT
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF HIGHLAND BEACH RO WTP
HB-TPW1
961556
755843
Start Test Date:
09-AUG-2001 0200
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
670
Horizontal K (ft/day):
Hours Pumped:
1030
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
260
Storativity:
Tested Interval Max. (ft BLS):
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2M HILL, OCTOBER 2001, TECH. MEMORANDUM- CONSTRUCTION & TESTING OF FLORIDAN AQUIFER TEST PRODUCTION WELL TP-1
Comments:
PACKER TEST 3 CONDUCTED FOR WQ AND SPECIFIC CAPACITY S.C.= 29.4 GPM/FT
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF HIGHLAND BEACH RO WTP
HB-TPW1
961556
755843
Start Test Date:
09-AUG-2001 0300
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
122
Horizontal K (ft/day):
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1290
Storativity:
Tested Interval Max. (ft BLS):
1460
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2M HILL, OCTOBER 2001, TECH. MEMORANDUM- CONSTRUCTION & TESTING OF FLORIDAN AQUIFER TEST PRODUCTION WELL TP-1
Comments:
PACKER TEST 4 CONDUCTED FOR WQ AND SPECIFIC CAPACITY S.C.= 4.7 GPM/FT
Page generated at: 04-OCT-2025 03:55 EDT
DBHYDRO Menu
|
DBHYDRO Home
|
SFWMD Home
|
User's Guide
|
What's New
|
FAQ
|
Comments?