DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
TOWN OF HIGHLAND BEACH RO WTP
HB-TPW2
962006
755978
Start Test Date:
14-MAR-2002 0000
Aquifer:
UPPER FLORIDAN AQUIFER (UFA)
Test Type:
APT
Transmissivity (ft2/day):
17769
Discharge Rate (gal/min):
3000
Horizontal K (ft/day):
94
Hours Pumped:
72
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1010
Storativity:
.06
Tested Interval Max. (ft BLS):
1200
Leakance (1/day):
No. Monitored Wells:
1
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
CH2MHILL, 2002. TECHNICAL MEMORANDUM ON THE CONSTRUCTION AND TESTING OF FLORIDAN AQUIFER TEST PRODUCTION WELL TP-2. TOWN OF HIGHLAND BEACH. JUNE, 2002.
Comments:
RECOMMENDED T IS AN AVERAGE OF VALUES CALCULATED FROM THE PUMPING AND RECOVERY DATA (RANGE: 14,547 F2/D - 21,540 FT2/D). TDS = 7,280 MG/L. SPECIFIC CAPACITY = 112 GPM/FT.