DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELD
HHRO-IW1
863971
578545
Start Test Date:
08-DEC-2009 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
15
Horizontal K (ft/day):
.55
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1839
Storativity:
Tested Interval Max. (ft BLS):
1856
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:
TDS = 6360: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 175
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELD
HHRO-IW1
863971
578545
Start Test Date:
09-DEC-2009 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
15.5
Horizontal K (ft/day):
.57
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1899
Storativity:
Tested Interval Max. (ft BLS):
1916
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:
TDS = 16100: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 159
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELD
HHRO-IW1
863971
578545
Start Test Date:
12-DEC-2009 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
11
Horizontal K (ft/day):
.49
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1973
Storativity:
Tested Interval Max. (ft BLS):
1991
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:
TDS = 26833: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 136
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELD
HHRO-IW1
863971
578545
Start Test Date:
26-JAN-2010 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
0.5
Horizontal K (ft/day):
.05
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2234
Storativity:
Tested Interval Max. (ft BLS):
2251
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:
TDS = 35333: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 21
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELD
HHRO-IW1
863971
578545
Start Test Date:
28-JAN-2010 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
6
Horizontal K (ft/day):
.48
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2399
Storativity:
Tested Interval Max. (ft BLS):
2417
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:
TDS = 26367: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 73
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELD
HHRO-IW1
863971
578545
Start Test Date:
29-JAN-2010 0000
Aquifer:
Test Type:
PACKER
Transmissivity (ft2/day):
Discharge Rate (gal/min):
8
Horizontal K (ft/day):
.79
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2639
Storativity:
Tested Interval Max. (ft BLS):
2657
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:
TDS = 37700: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 58
Page generated at: 04-OCT-2025 11:42 EDT
DBHYDRO Menu
|
DBHYDRO Home
|
SFWMD Home
|
User's Guide
|
What's New
|
FAQ
|
Comments?