DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELDHHRO-IW2863918578699

Start Test Date:21-DEC-2009 0000Aquifer:
Test Type:PACKERTransmissivity (ft2/day):
Discharge Rate (gal/min):5.5Horizontal K (ft/day):.37
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):1884Storativity:
Tested Interval Max. (ft BLS):1901Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:TDS = 13910: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 143



SitePumped WellX-Coord(ft)Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELDHHRO-IW2863918578699

Start Test Date:08-FEB-2010 0000Aquifer:
Test Type:PACKERTransmissivity (ft2/day):
Discharge Rate (gal/min):22Horizontal K (ft/day):1.11
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2049Storativity:
Tested Interval Max. (ft BLS):2067Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:TDS = 29000: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 110



SitePumped WellX-Coord(ft)Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELDHHRO-IW2863918578699

Start Test Date:09-FEB-2010 0000Aquifer:
Test Type:PACKERTransmissivity (ft2/day):
Discharge Rate (gal/min):30Horizontal K (ft/day):2.02
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2569Storativity:
Tested Interval Max. (ft BLS):2587Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:TDS = 36467: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 86



SitePumped WellX-Coord(ft)Y-Coord (ft)
HIALEAH HEIGHTS REVERSE OSMOSIS WELLFIELDHHRO-IW2863918578699

Start Test Date:11-FEB-2010 0000Aquifer:
Test Type:PACKERTransmissivity (ft2/day):
Discharge Rate (gal/min):1Horizontal K (ft/day):.08
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2259Storativity:
Tested Interval Max. (ft BLS):2277Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT SWS, City of Hialeah Reverse Osmosis Water Treatment Plant Injecion Wells IW-1 & IW-2 and Dual-zone Monitor Well DZMW-1 Completion Report. Nov. 12, 2010
Comments:TDS = 35900: Reporting hydraulic conductivity from recovery analysis: Maximum drawdown [ft] = 63

Page generated at: 04-OCT-2025 08:25 EDT

DBHYDRO Menu  |   DBHYDRO Home  |   SFWMD Home  |   User's Guide  |   What's New  |   FAQ |  Comments?