DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
INDIANTOWN COGENERATION PLANT - FAS
ICW-2
814302
983907
Start Test Date:
25-OCT-1993 0900
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
APT
Transmissivity (ft2/day):
27406
Discharge Rate (gal/min):
1194
Horizontal K (ft/day):
Hours Pumped:
29
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
738.7
Storativity:
.0003
Tested Interval Max. (ft BLS):
1262.8
Leakance (1/day):
.0032
No. Monitored Wells:
2
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
BECHTEL POWER CORPORATION, APT REPORT INDIANTOWN COGENERATION PROJECT
Comments:
IPW-2 WAS TESTED AT TWO ZONES DURING CONSTRUCTION
Well Name
X Coord(ft)
Y Coord(ft)
Analysis Method
DistancefromProductionWell(ft)
Max.Drawdown(ft)
Transmissivity(ft**2/day)
Storativity
Leakance
IPW-2
814122
983806
HANTUSH-JACOB (1955)
365
27406
.0003
.0032
IPW-2
814122
983806
THEIS RECOVERY
0
38770
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
INDIANTOWN COGENERATION PLANT - FAS
ICW-2
814302
983907
Start Test Date:
14-DEC-1993 0915
Aquifer:
AVON-PARK PERMEABLE ZONE
Test Type:
APT
Transmissivity (ft2/day):
307487
Discharge Rate (gal/min):
2627
Horizontal K (ft/day):
Hours Pumped:
26
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1482
Storativity:
.0013
Tested Interval Max. (ft BLS):
1660
Leakance (1/day):
.0032
No. Monitored Wells:
1
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
BECHTEL, 1994. UPPER FLORIDAN AQUIFER AQUIFER PERFORMANCE TEST REPORT. VOL.1; INDIANTOWN COGENERATION PROJECT. MARCH 1994
Comments:
LEAKANCE IS FOR MC1 - UNIT BETWEEN UPPER AND MIDDLE FLORIDAN