DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
NORTH COLLIER COUNTY WASTE WATER TREATMENT PLANTMC-5003433672695082

Start Test Date:03-FEB-1995 1010Aquifer:MID-HAWTHORN AQUIFER
Test Type:APTTransmissivity (ft2/day):2580
Discharge Rate (gal/min):540Horizontal K (ft/day):22
Hours Pumped:70Vertical K (ft/day):
Tested Interval Min. (ft BLS):398Storativity:.00087
Tested Interval Max. (ft BLS):514Leakance (1/day):.00015
No. Monitored Wells:1Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT MISSIMER INTERNATIONAL, OCTOBER 1995. COLLIER COUNTY UTILITIES BRACKISH WATER WELLFIELD STUDY. PROJECT FH4-26.
Comments:PARAMETER VALUES DETERMINED FROM AVERAGE OF COOPER '63 AND JACOB '50 VALUES. LEAKANCE FROM COOPER ONLY. * IN ANALYSIS INFO, METHOD IS LISTED AS OTHER IS COOPER 1963 AND THAT LISTED AS UNKNOWN IS JACOB 1950.

Well Name X Coord
(ft)
Y Coord
(ft)
Analysis Method Distance
from
Production
Well
(ft)
Max.
Drawdown
(ft)
Transmissivity
(ft**2/day)
Storativity Leakance
MC-5000
433701
694941
OTHER
565
2580
.00087
.00015
MC-5000
433701
694941
UNKNOWN
565
2955
.000098

Page generated at: 28-SEP-2024 20:23 EDT