DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
NORTH LEE COUNTY WATER TREATMENT PLANT
NLCWTP-IW1
397889
872376
Start Test Date:
05-JUN-2003 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
797.2
Discharge Rate (gal/min):
78
Horizontal K (ft/day):
20.7
Hours Pumped:
4
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1636
Storativity:
Tested Interval Max. (ft BLS):
1674
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
MWH, APRIL, 2004; NORTH LEE COUNTY WATER TREATMENT PLANT, CLASS I INJECTION WELL AND DUAL ZONE MONITORING WELL DRILLING AND TESTING REPORT.
Comments:
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
NORTH LEE COUNTY WATER TREATMENT PLANT
NLCWTP-IW1
397889
872376
Start Test Date:
06-JUN-2003 0001
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
15
Discharge Rate (gal/min):
68
Horizontal K (ft/day):
.39
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1464
Storativity:
Tested Interval Max. (ft BLS):
1502
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
MHW, APRIL, 2004, MHW, APRIL, 2004; NORTH LEE COUNTY WATER TREATMENT PLANT, CLASS I INJECTION WELL AND DUAL ZONE MONITORING WELL DRILLING AND TESTING REPORT.
Comments:
VALUES ARE THE AVERAGE OF TWO MEASUREMENTS.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
NORTH LEE COUNTY WATER TREATMENT PLANT
NLCWTP-IW1
397889
872376
Start Test Date:
12-AUG-2003 0002
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
.32
Discharge Rate (gal/min):
1.25
Horizontal K (ft/day):
.016
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2280
Storativity:
Tested Interval Max. (ft BLS):
2300
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
MWH, APRIL, 2004; NORTH LEE COUNTY WATER TREATMENT PLANT, CLASS I INJECTION WELL AND DUAL ZONE MONITORING WELL DRILLING AND TESTING REPORT.
Comments:
VALUES ARE THE AVERAGE OF TWO MEASUREMENTS.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
NORTH LEE COUNTY WATER TREATMENT PLANT
NLCWTP-IW1
397889
872376
Start Test Date:
13-AUG-2003 0003
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
.23
Discharge Rate (gal/min):
1.25
Horizontal K (ft/day):
.012
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2372
Storativity:
Tested Interval Max. (ft BLS):
2392
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
MWH, APRIL, 2004; NORTH LEE COUNTY WATER TREATMENT PLANT, CLASS I INJECTION WELL AND DUAL ZONE MONITORING WELL DRILLING AND TESTING REPORT.
Comments:
VALUES ARE THE AVERAGE OF TWO MEASUREMENTS.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
NORTH LEE COUNTY WATER TREATMENT PLANT
NLCWTP-IW1
397889
872376
Start Test Date:
14-AUG-2003 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
.83
Discharge Rate (gal/min):
2.5
Horizontal K (ft/day):
.042
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2445
Storativity:
Tested Interval Max. (ft BLS):
2465
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
MWH, APRIL, 2004; NORTH LEE COUNTY WATER TREATMENT PLANT, CLASS I INJECTION WELL AND DUAL ZONE MONITORING WELL DRILLING AND TESTING REPORT.
Comments:
VALUES ARE THE AVERAGE OF TWO MEASUREMENTS.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
NORTH LEE COUNTY WATER TREATMENT PLANT
NLCWTP-IW1
397889
872376
Start Test Date:
15-AUG-2003 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
1.83
Discharge Rate (gal/min):
5
Horizontal K (ft/day):
.1
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2567
Storativity:
Tested Interval Max. (ft BLS):
2585
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
MWH, APRIL, 2004; NORTH LEE COUNTY WATER TREATMENT PLANT, CLASS I INJECTION WELL AND DUAL ZONE MONITORING WELL DRILLING AND TESTING REPORT.
Comments:
VALUES ARE THE AVERAGE OF TWO MEASUREMENTS.
Page generated at: 04-OCT-2025 06:37 EDT
DBHYDRO Menu
|
DBHYDRO Home
|
SFWMD Home
|
User's Guide
|
What's New
|
FAQ
|
Comments?