DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
WEST PALM BEACH WTP - ASRPB-1692961920867330

Start Test Date:01-FEB-1997 0001Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:APTTransmissivity (ft2/day):108000
Discharge Rate (gal/min):700Horizontal K (ft/day):
Hours Pumped:24Vertical K (ft/day):
Tested Interval Min. (ft BLS):985Storativity:.0008
Tested Interval Max. (ft BLS):1200Leakance (1/day):
No. Monitored Wells:1Specific Capacity (gpm/ft):
SourceReferenceCitation Id
US GEOLOGICAL SURVEY Reese, 2002. Inventory and Review of Aquifer Storage & Recovery in Southern Florida. USGS WRI 02-4036
Comments:RECOVERY WAS ALLOWED FOLLOWING STEP TEST OF ASR-1, PRIOR TO INITIAION OF MULTI-WELL TEST. LARGE DEVIATION FROM THEIS CURVE DURING LATE TIME, BUT LEAKY AQUIFER SOLUTION NOT USED.

Well Name X Coord
(ft)
Y Coord
(ft)
Analysis Method Distance
from
Production
Well
(ft)
Max.
Drawdown
(ft)
Transmissivity
(ft**2/day)
Storativity Leakance
PB-1693
961831
867127
COOPER-JACOB APPROXIMATION
100
138000
.0001
PB-1693
961831
867127
THEIS
100
108000
.0008

Page generated at: 28-SEP-2024 20:11 EDT

DBHYDRO Menu  |   DBHYDRO Home  |   SFWMD Home  |   User's Guide  |   What's New  |   FAQ |  Comments?