DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
19-JUN-2002 0400
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
21.4
Discharge Rate (gal/min):
9.6
Horizontal K (ft/day):
.6
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2319
Storativity:
Tested Interval Max. (ft BLS):
2350
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS PAPADOPULOS-COOPER, 1967 - FROM RECOVERY.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
22-JUN-2002 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
13821
Discharge Rate (gal/min):
81.1
Horizontal K (ft/day):
130.39
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2160
Storativity:
Tested Interval Max. (ft BLS):
2264
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS TURCAN, 1963 - FROM DRAWDOWN.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
25-JUN-2002 0100
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
.69
Discharge Rate (gal/min):
.8
Horizontal K (ft/day):
.041
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1920
Storativity:
Tested Interval Max. (ft BLS):
1936
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS PAPADOPULOS-COOPER, 1967 - FROM DRAWDOWN.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
28-JUN-2002 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
3.54
Discharge Rate (gal/min):
1.9
Horizontal K (ft/day):
.21
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1760
Storativity:
Tested Interval Max. (ft BLS):
1776
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS TURCAN, 1963 - FROM DRAWDOWN.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
29-JUN-2002 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
2678
Discharge Rate (gal/min):
82.7
Horizontal K (ft/day):
160.44
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1520
Storativity:
Tested Interval Max. (ft BLS):
1536
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS TURCAN, 1963 - FROM DRAWDOWN.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
04-JUL-2002 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
6.96
Discharge Rate (gal/min):
4.2
Horizontal K (ft/day):
.42
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1552
Storativity:
Tested Interval Max. (ft BLS):
1568
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS TURCAN, 1963 - FROM DRAWDOWN.
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
29-AUG-2002 0200
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
15.5
Discharge Rate (gal/min):
7.3
Horizontal K (ft/day):
.31
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
1859.2
Storativity:
Tested Interval Max. (ft BLS):
1906.9
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS PAPADOPULOS-COOPER, 1967 - FROM DRAWDOWN
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
06-OCT-2002 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
5.24
Discharge Rate (gal/min):
3
Horizontal K (ft/day):
.26
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2744.9
Storativity:
Tested Interval Max. (ft BLS):
2764.7
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS TURCAN, 1963 - FROM DRAWDOWN
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
08-OCT-2002 0200
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
45.4
Discharge Rate (gal/min):
19.9
Horizontal K (ft/day):
2.24
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2361.9
Storativity:
Tested Interval Max. (ft BLS):
2381.7
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS PAPADOPULOS-COOPER, 1963 - FROM DRAWDOWN
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
PORT ST. LUCIE LTC WATER TREATMENT PLANT
PSLLTC-MW1
850743
1104484
Start Test Date:
09-OCT-2002 0000
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
PACKER
Transmissivity (ft2/day):
105.4
Discharge Rate (gal/min):
33.7
Horizontal K (ft/day):
.95
Hours Pumped:
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
2426.9
Storativity:
Tested Interval Max. (ft BLS):
2536.7
Leakance (1/day):
No. Monitored Wells:
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
ARCADIS. 2003. OPERATIONAL TESTING REQUEST. CITY OF PORT ST. LUCIE CLASS I INJECTION WELL SYSTEM.
Comments:
ANALYSIS METHOD IS TURCAN, 1963 - FROM DRAWDOWN
Page generated at: 29-JUN-2024 05:30 EDT
DBHYDRO Menu
|
DBHYDRO Home
|
SFWMD Home
|
User's Guide
|
What's New
|
FAQ
|
Comments?