DBHYDRO       reports

Hydraulic Details

SitePumped WellX-Coord(ft)Y-Coord (ft)
PORT ST. LUCIE WESTPORT WASTEWATER TREATMENT PLANTPSLWPT-IW18663891055243

Start Test Date:26-APR-2003 0000Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:PACKERTransmissivity (ft2/day):13.6
Discharge Rate (gal/min):8.8Horizontal K (ft/day):.75
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2880Storativity:
Tested Interval Max. (ft BLS):2897.7Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT ARCADIS-CONSTRUCTION & TESTING SUMMARY REPORT- WESTPORT WWTP INJECTION WELL SYSTEM- CITY OF PT. ST. LUCIE-JULY 2004
Comments:STRADDLE PACKER TEST #6 (1 OF 5) ANALYSIS: TURCAN (1963)



SitePumped WellX-Coord(ft)Y-Coord (ft)
PORT ST. LUCIE WESTPORT WASTEWATER TREATMENT PLANTPSLWPT-IW18663891055243

Start Test Date:27-APR-2003 0000Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:PACKERTransmissivity (ft2/day):9.21
Discharge Rate (gal/min):6.6Horizontal K (ft/day):.51
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2636Storativity:
Tested Interval Max. (ft BLS):2653.7Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT ARCADIS-CONSTRUCTION & TESTING SUMMARY REPORT- WESTPORT WWTP INJECTION WELL SYSTEM- CITY OF PT. ST. LUCIE-JULY 2004
Comments:STRADDLE PACKER TEST #7 (2 OF 5) ANALYSIS: TURCAN (1963)



SitePumped WellX-Coord(ft)Y-Coord (ft)
PORT ST. LUCIE WESTPORT WASTEWATER TREATMENT PLANTPSLWPT-IW18663891055243

Start Test Date:29-APR-2003 0000Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:PACKERTransmissivity (ft2/day):.43
Discharge Rate (gal/min):2Horizontal K (ft/day):.23
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2580Storativity:
Tested Interval Max. (ft BLS):2597.7Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT ARCADIS-CONSTRUCTION & TESTING SUMMARY REPORT- WESTPORT WWTP INJECTION WELL SYSTEM- CITY OF PT. ST. LUCIE-JULY 2004
Comments:STRADDLE PACKER TEST #8 (3 OF 5) ANALYSIS: COOPER-JACOB (1946)



SitePumped WellX-Coord(ft)Y-Coord (ft)
PORT ST. LUCIE WESTPORT WASTEWATER TREATMENT PLANTPSLWPT-IW18663891055243

Start Test Date:02-MAY-2003 0000Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:PACKERTransmissivity (ft2/day):3.79
Discharge Rate (gal/min):2.6Horizontal K (ft/day):.21
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2217Storativity:
Tested Interval Max. (ft BLS):2234.7Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT ARCADIS-CONSTRUCTION & TESTING SUMMARY REPORT- WESTPORT WWTP INJECTION WELL SYSTEM- CITY OF PT. ST. LUCIE-JULY 2004
Comments:STRADDLE PACKER TEST #9 (4 OF 5) ANALYSIS: TURCAN (1963) TRANSMISSITIVY ESTIMATED FROM DRAWDOWN ONLY



SitePumped WellX-Coord(ft)Y-Coord (ft)
PORT ST. LUCIE WESTPORT WASTEWATER TREATMENT PLANTPSLWPT-IW18663891055243

Start Test Date:03-MAY-2003 0000Aquifer:FLORIDAN AQUIFER SYSTEM
Test Type:PACKERTransmissivity (ft2/day):103
Discharge Rate (gal/min):33.1Horizontal K (ft/day):2
Hours Pumped:Vertical K (ft/day):
Tested Interval Min. (ft BLS):2830Storativity:
Tested Interval Max. (ft BLS):2880.7Leakance (1/day):
No. Monitored Wells:Specific Capacity (gpm/ft):
SourceReferenceCitation Id
CONSULTANT ARCADIS-CONSTRUCTION & TESTING SUMMARY REPORT- WESTPORT WWTP INJECTION WELL SYSTEM- CITY OF PT. ST. LUCIE-JULY 2004
Comments:STRADDLE PACKER TEST #10 (5 OF 5) ANALYSIS: TURCAN (1963)