DBHYDRO
reports
Hydraulic Details
Site
Pumped Well
X-Coord(ft)
Y-Coord (ft)
SO. COLLIER COUNTY WASTE WATER TREATMENT PLANT - FAS
MC-5060
431503
667245
Start Test Date:
26-JUL-2000 0900
Aquifer:
FLORIDAN AQUIFER SYSTEM
Test Type:
APT
Transmissivity (ft2/day):
3062
Discharge Rate (gal/min):
320
Horizontal K (ft/day):
Hours Pumped:
96
Vertical K (ft/day):
Tested Interval Min. (ft BLS):
650
Storativity:
.000085
Tested Interval Max. (ft BLS):
762
Leakance (1/day):
.00013
No. Monitored Wells:
1
Specific Capacity (gpm/ft):
Source
Reference
Citation Id
CONSULTANT
MDM/MISSIMER INTERNATIONAL INC. OCTOBER, 2000. COLLIER COUNTY PUBLIC WORKS SOUTHERN REVERSE OSMOSIS WELLFIELD STUDY, COLLIER COUNTY, FL. PROJECT NO: FH8-812/9086-28655-DN.FWF
Comments:
PARAMETER VALUES TAKEN FROM CURVE MATCHING METHOD OF DRAWDOWN, STRAIGHT LINE METHOD OF DRAWDOWN AND RECOVERY AT MON. WELL MC-5067.
Well Name
X Coord(ft)
Y Coord(ft)
Analysis Method
DistancefromProductionWell(ft)
Max.Drawdown(ft)
Transmissivity(ft**2/day)
Storativity
Leakance
MC-5067
432165
666434
JACOB STRAIGHT-LINE (1952)
807
3048
.000098
MC-5067
432165
666434
OTHER
807
2874
.000063
.00013
MC-5067
432165
666434
RECOVERY
807
3142
.000094
Page generated at: 05-JUL-2024 05:06 EDT